Call Us Toll Free At 1-800-843-6036

Place On-Line Order More Potter Products E-Mail Us MidSouths' Home Page

               Industrial Switches


MODELS AVAILABLE:  ADPS SERIES, DPS-50 & IFS SERIES


ADPS

ADJUSTABLE DEADBAND PRESSURE SWITCH

adjustable deadband pressure switchADPS

ADJUSTABLE

DEADBAND

PRESSURE

       SWITCH         

 

 

 

Listing/Approvals:
  •  UL Standard 508 Guide (NKPZ) and CSA Standard C22.2 No. 14-M Class (321106) for Pressure Operated Industrial Control Equipment.
  • UL Standard 873 Guide (XAPX) and CSA Standard C22.2 No. 24 Class (481302) for Temperature Indicating and Regulating Equipment.
  • CE Marked

Ambient/Media Temperature Range:

  • -4ºF to 180ºF (-20ºc to 82ºC)
Adjusting Operating Range Minimum Deadband Proof Pressure Factory Setting
25-300 PS/G 12 PS/G 400 PS/G 90/60 PS/G
General Description

Ideal for jockey pumps, air compress, and fire pumps, the model ADPS is an Adjustable Deadband Pressure Switch with independent set and reset points which are adjustable throughout the entire operating range of the switch.  The minimum deadband (minimum span between set and reset points) may be obtained at any point in the operating range of the switch.  A change in pressure greater than the high setting will reposition the switch mechanism to open or close a single snap-action electrical switch.

This control device is designed for use as an operating control in applications sensing air, water, or any fluid not harmful to the pressure connection, diaphragm or nitrile pressure-sealing o-ring.  Where an operating control would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit controls) that protect against, or systems (alarm, supervisory systems) that warn of control failure.

This device is not intended for applications in explosive environments or use with hazardous fluids.

Construction:
  • NEMA Type 4X Enclosure for indoor or outdoor use. (To maintain 4X rating, use appropriate Type 4 conduit hub.) 
  • Forged Brass or 316S.S. Pressure Connections (1/2 HP Brass only)
  • Aluminum Diecast Base with Polymer Enclosure
  • Beryllium Copper Diaphragm (Stainless steel isolator diaphragm included for protection of beryllium copper diaphragm on models with stainless steel pressure connection.)
  • Nitrile Pressure Sealing O-ring

Switch Contact:  Snap-Action SPDT (Form C)     

  • 15 Amps @ 125/250/480 VAC         
  • 22 Amps @125/250/480*     
  •  1 HP @ 250 VAC*       
  • 1/2 HP @ 125 VAC* 
  • 1/4 HP @ 250 VAC    
  •  1/8 HP @ 125 VAC                   

*Only on Model number ADPS-300-1B 1/2 HP

 

 

ORDERING INFORMATION

Model # Adjustable Operating Range Minimum Deadband Proof Pressure Pressure Connection Diaphragm
ADPS-300-1B 25-300 PSIG 12 PSIG 400 PSIG 1/4" NPT Brass Beryllium Copper
ADPS-300-1S 25-300 PSIG 12 PSIG 400 PSIG 1/4" NPT 316 S.S. Beryllium Copper w/316 S.S. Isolator
ADPS-300-2S 25-300 PSIG 12 PSIG 400 PSIG 3/8" NPT 316 S.S. Beryllium Copper w/316 S.S. Isolator
ADPS-600-1B 50-600 PSIG 25 PSIG 650 PSIG 1/4" NPT Brass Beryllium Copper
ADPS-600-1S 50-600 PSIG 25 PSIG 650 PSIG 1/4" NPT 316 S.S. Beryllium Copper w/316 S.S. Isolator
ADPS-600-2S 50-600 PSIG 25 PSIG 650 PSIG 3/8" NPT 316 S.S. Beryllium Copper w/316 S.S. Isolator
ADPS-300-1B-1/2 HP 25-300 PSIG 12 PSIG 400 PSIG 1/4" NPT Brass Beryllium Copper

PRICING

Model Number

Price Each

ADPS-300-1B

$209.99

ADPS-300-1S

$269.99

ADPS-300-2S

$269.99

ADPS-600-1B

$209.99

ADPS-600-1S

$269.99

ADPS-600-2S

$269.99

ADPS-300-1B 1/2 HP

$209.99

 


ADPS

ADJUSTABLE DEADBAND PRESSURE SWITCH-OPEN FRAME

adps, adjustable deadband pressure switch, open frameADPS

ADJUSTABLE

DEADBAND

SWITCH

OPEN FRAME

 

Recognition:
  • Recognized component to UL Standard 508.  CSA Standard C22.2 No. 14-M Class (321106) for Pressure Operated Industrial Control Equipment.
  • CSA Standard C22.2 No. 24 Class (481302) for Temperature Indicating and Regulating Equipment.
  • CE Marked

Ambient/Media Temperature Range:

  • -4ºF to 180ºF (-20ºC to 82ºC)

 

General Description

The model ADPS is an Adjustable Deadband Pressure Switch with independent set and reset points which are adjustable throughout the entire operating range of the switch.  The minimum deadband (minimum span between set and reset points) may be obtained at any point in the operating range of the switch.  A change in pressure greater than the high setting will reposition the switch mechanism to open or close a single snap-action electrical switch.

This control device is designed for use as an operating control in applications sensing air, water, or any fluid not harmful to the pressure connection, diaphragm or nitrile pressure-sealing o-ring.  Where an operating control would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit controls) that protect against, or systems (alarm, supervisory systems) that warn of control failure.

This device is not intended for applications in explosive environments or use with hazardous fluids.

Construction:
  • Forged Brass or 316 S.S. Pressure Connections
  • Aluminum Diecast Base
  • Beryllium Copper Diaphragm (Stainless steel isolator diaphragm included for protection of beryllium copper diaphragm on models with stainless steel pressure connection.)
  • Nitrile Pressure Sealing O-ring

Switch Contact:

  • Snap-Action SPDT (Form C)
  • 15 Amps @ 125/250/480 VAC
  • 1/8 HP @ 125 VAC
  • 1/4 HP @ 250 VAC

CAUTION:  Direct control of motors with HP ratings greater than the ratings shown could result in premature failure of the ADPS or significantly shorten operating life

Adjustable Operating Range Minimum Deadband Proof Pressure Factory Setting
25-300 PSIG 12 PSIG 400 PSIG 90/60 PSIG

ORDERING INFORMATION

Model # Adjustable Operating Range Minimum Deadband Proof Pressure Pressure Connection Diaphragm
ADPS-300-1B-0 25-300 PSIG 12 PSIG 400 PSIG 1/4" NPT Brass Beryllium Copper
ADPS-300-1S-0 25-300 PSIG 12 PSIG 400 PSIG 1/4" NPT 316 S.S. Beryllium Copper w/316 S.S. Isolator
ADPS-600-1B-0 50-600 PSIG 25 PSIG 650 PSIG 1/4" NPT Brass Beryllium Copper
ADPS-600-1S-0 50-600 PSIG 25 PSIG 650 PSIG 1/4" NPT 316 S.S. Beryllium Copper w/316 S.S. Isolator

PRICING

Model Number Price Each
ADPS-300-1B-0 $159.99
ADPS-300-1S-0 $259.99
ADPS-600-1B-0 $159.99
ADPS-600-1S-S $259.99

 


DPS-50

DIFFERENTIAL PRESSURE SWITCH

differential pressure switchDifferential

Pressure

Switch

DPS-50

$169.99 EACH

UL listed and CSA Approved

Maximum Rated Pressure:  250 PSI

Maximum Working Pressure:  180 PSI

Pressure Connections:  Brass 1/4-18 NPT Female

General Description

The Model DPS-50 is a differential pressure switch used to monitor the difference in pressure between two pressure sources.  A change in pressure between the high and low pressure ports greater than the differential pressure setting (8-50 PSID range) will reposition the switch mechanism to open or close a single electrical circuit by means of a snap-action electrical switch.  This control device is designed for applications sensing air, water or any fluid not harmful to brass or silicone and not classified as a hazardous fluid.

This control device is designed for use only as an operating control.  Where an operating control failure would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit controls) that protect against, or systems (alarm, supervisory systems) that warn of control failure.

Ambient Temperature Range:  -40º/180ºF (40º/82ºC)

Media Temperature Range:  32º/250ºF (0º/121ºC)

 

Differential Proof Pressure:  180 PSID    (Maximum allowable pressure difference across high/low pressure ports.)

Enclosure:  NEMA Type 1 (for indoor use only) Formed sheet metal with powdercoat finish.  (Not for use in hazardous locations.)

Switch Contacts:

  • Snap-Action SPDT (form C) Switch
  • 22 amps @ 125/250/480 VAC

Conduit Entrance:  Opening for 1/2" conduit

Motor Rating:  120VAC, 240VAC

Horsepower: 1/2,1

AC F.L.A.:  9.8, 8.0

AC L.R.A.:  58.8 ,48.0

CAUTION:  This device is not intended for applications   in explosive environments.

 


IFS SERIES

INDUSTRIAL FLOW SWITCHES

"NOT" SOLD FOR HVAC APPLICATIONS

Industrial Flow

Switch

IFS 1 & 2

Industrial Flow

Switch

IFS-WPS

General Description

The Model IFS is a flow switch used in liquid flow lines carrying water or any fluid not harmful to brass, stainless steel or flourosilicone, and not classified as a hazardous fluid.

This switch can serve as a way to start and stop electrically operated equipment when a flow or no flow condition occurs in a variety of applications.

This device is designed for use only as an operating control.  Where an operating control failure would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit controls) that protect against, or systems (alarm, supervisory systems) that warn of control failure.

Usage:  For pipe sized 1" to 8"

Caution:  This device is not intended for applications in explosive environments.

  Enclosure Ambient Temp. Range Media Temp. Range Turning Radius
IFS-1 & IFS-2 NEMA 1 32ºF to 176ºF (0ºC to 80ºC) 32ºF to 250ºF (0ºC to 121ºC) 2.83"
IFS-WPS NEMA 4 32ºF to 150ºF (0ºC to 66ºC) -20ºF to 250ºF    (-29ºC to 121ºC) 1.88"
Listing/Approvals:
  • UL Guide (NKPZ) for industrial control equipment per UL Standard 508 Industrial
  • UL Guide (MFHX) for heating/cooling appliance switch per UL Standard 353 Limit Controls
  • CSA Class (321106) for industrial control equipment per CSA Standard C22.2 No. 14-M Industrial Control Equipment

Maximum Service Pressure:  250 PSI

Enclosure:      (Not for use in hazardous locations)

  • NEMA Type 1 (For indoor use only)
  • NEMA Type 4 (IFS-WPS only)  

Contacts:

  • IFS-1/IFS-HC-1 Series:  One SPDT (Form C) switch
  • IFS-WPS Series:  One SPDT (Form C) switch
  • IFS-2/IFS-HC-2 Series:  Two sets of SPDT (Form C) switches to provide versatility in wiring two separate circuits.
  IFS- 1 & IFS-2 Models IFS-1 & IFS-2 HC Models IFS-WPS Models
Current Rating 125/250 VAC 15 Amps 22 Amps 10 Amps
125 VDC 0.5 Amps - 0.5 Amps
250 VDC 0.25 Amps - 0.25 Amps
Horsepower 120 VAC 1/8 HP 1/2 HP 1/3 HP
240 VAC 1/4 HP 1 HP 1/3 HP
AC FLA 120 VAC 3.8 9.8 7.2
240 VAC 2.9 8.0 3.6
AC LRA 120 VAC 22.8 58.8 43.2
240 VAC 17.4 48.0 21.6
Pilot Rating 120/240 VAC 125 VA 125 VA 332 VA

ORDERING & PRICING INFORMATION

NOT SOLD FOR HVAC APPLICATIONS

MODEL NUMBER PRICE EACH  
IFS-1   CE Marked
IFS-2   CE Marked
IFS-HC-1    
IFS-HC-2    
IFSS-1   CE Marked
IFSS-2   CE Marked
IFSS-HC-1    
IFSS-HC-2    
IFS-WPS   CE Marked
IFSS-WPS   CE Marked

1-800-843-6036

Place On-Line Order More Potter Products E-Mail Us MidSouths' Home Page

Prices Subject to Change Without Notice.

Product Design and Specifications Subject to Change Without Notice.

Visit midsouthelectronics.com for more electronic solutions